09 October 2008

Completed expert's surveys of building structures

Safety analysis and construction design of protecting the deflected GAS PIPE structure in Katowice

In 2008, a construction machine hit a steel structural support column during earth works in the area of gas pipe route. As a result, a risky deflection of some support columns was observed. As part of a team of two surveyors, I analysed safety of the damaged structure and prepared the concept of temporary protection measures. The issue was urgent due to the real risk of construction disaster.

 

Problem outline and description of supporting structure

 

A pipe-bridge of two-branch steel columns at two different heights, was the supporting structure of the gas pipe. Two pipelines were directly supported on lower columns (ca. 6 m high). Higher two-branch columns (ca. 11 m high) and a spandler beam were the support for the pipe running over the hardened temporary road. 

Careless operation of the construction machine while performing the earth works under the gas pipe damaged (buckling) a branch of the lower two-branch column of the pipe-bridge. The damaged column caused the inclination of other adjacent columns and thus, caused the state of unstable equilibrium of the supporting structure which was dangerous due to the presence of operating gas pipe. 

 

Method of structure protection

 

Computational analysis of safety of gas pipe steel supporting structure indicated the necessity of applying reinforcement in the form of over ten knee braces. Diagonal knee braces were performed as steel pipes fixed to horizontal channels which transmitted vertical impact to soil through railway wooden sleepers. The steel knee brace transmitted horizontal impact to steel stays welded on outer branches of the protected columns. It was necessary to protect the higher column of the pipe-bridge by using the additional local reinforcement by welding four iron angles on its both branches.

author: Mariusz Jaśniok

  1. pl
  2. en
Logo prezentujące najlepszych w sewisie OFERTEO w roku 2019

Links to recommended applications

 

  • NOZBE - great application for managing tasks and time 

  • WEBWAVE - Polish website creator, in which I made this site 

Company's data

 

Prof. Mariusz Jaśniok - rzeczoznawca budowlany

address: PL 44-121 Gliwice, 45/4 Szafirowa

NIP: 626-192-52-08   REGON: 362494036

email: mariusz.jasniok@corrtest.pl

website: corrtest.pl

mobile: +48 692 246 710

Menu 

Links to external sites

 

  • FULL PROFESSOR at the Silesian University of Technology

  • VICE DEAN for Education of Faculty of Civil Engineering of SUT

 

  • ORCID - 0000-0002-7628-0710 

  • RESEARCHGATE - international social network for scientists  

  • AKADEMIA.edu - international social network for scientists 

  • WoS - the Web of Science database maintained by Clarivate

  • SCOPUS - scientific database maintained by Elsevier

  • GOOGLE SCHOLAR - professional browser of scientific papers

  • YOUTUBE - channel of CorrTEST company on YouTube 

  • LINKED.IN - social network for business and professional contacts

webmaster: Mariusz Jaśniok

Logo prezentujące najlepszych w sewisie OFERTEO w roku 2019
Logo prezentujące najlepszych w sewisie OFERTEO w roku 2018